The HVAC system plays a very important role here to provide and maintain a stable specific condition/environment, so that the electrical and electronic equipments in the E-House can operate at its optimum performance, besides prolonging the equipment's life span.
  
 
Typical E-House Room's Requirement

GENERAL SWITCHGEAR ROOM
 
 Room Temperature
26°C±3°C 
 Relative Humidity
50% ±10%
 Room Differential Pressurization α Outdoor
25 Pa
EMERGENCY SWITCHBOARD ROOM
 
 Room Temperature
26°C±3°C 
 Relative Humidity
50% ±10%
 Room Differential Pressurization α Outdoor
25 Pa
TRANSFORMER ROOM
 
 Room Temperature
~36°C 
 Relative Humidity
50% ±10%
 Room Differential Pressurization α Outdoor
25 Pa
BATTERY ROOM
 
 Room Temperature
26°C±3°C 
 Relative Humidity
50% ±10%
 Room Differential Pressurization α Outdoor
25 Pa
 Air Recirculation
100% Exhaust Out

 

.